  • Power supply: AC85-265V power,D:DC24V power, 20W rated power output
  • IO:8xDI/6xDO( Relay-type )
  • Port:RS422, RS485,1 BD board supported
  • Protocol: LX3V-0806MR-A(D)1 :1S NO PROTOCOL, LX3V-0806MR-A(D)2 :2N NO PROTOCOL

4,975.00 5,860.00 GST Extra

Out of stock

The Wecon LX3V series, model LX3V-0806MR (LX3V0806MR), operates in Round Scan/Interrupt mode and supports programming in Instruction List/Ladder format. The system’s 16K storage capacity supports downloading and monitoring through a serial programming cable or mini USB.

For communication, it features COM1 with RS422 or RS485 compatibility. COM2 supports RS485. Designed to withstand various operating conditions. It operates within a temperature range of 0 to 55℃. Storage temperatures range from -20 to 70℃. It maintains functionality in environments with humidity levels between 5% and 85% RH (without condensation). It meets JIS C 0040 Standard for shock resistance.

The power supply accommodates AC 85-265V at 50-60Hz or DC 24V±10%, with a power outage time of 10ms and a power fuse rating of 250V 3.15A. By keeping rush current minimal, the PLC ensures stable operation, with power consumption under 35W. This PLC utilizes relay output for control functions. Additionally, it maintains mechanistic insulation and achieves a response time of under 10ms.

Our engineers has entered all the specification details about this PLC according to the datasheet. Although errors may occur during the process. All trademarks and trade names used on our site  are the property of their respective owners.

Weight 950 g
Dimensions 20 × 18 × 12 cm
Brands

Wecon

Condition

New

BrandWecon
SeriesLX3V
Model NoLX3V-0806MR
Running ModeRound Scan/ Interrupt
ProgrammingInstruction List/ Ladder
Total InstructionsBasic Instructions: 27 / Applied Instruction: 138
Execute timeBasic Instructions: 0.06us / Applied Instruction: 1~10us
System Storage16K
Download/ MonitoringSerial Programming Cable / Mini USB
External Interrupt6 Channels
Timer Interrupt3 Channels
Holding AddressesAdjustable
StorageFLASH
FilterFor all X input terminals
Serial PortCOM1: RS422 or RS485 / COM2: RS485
TemperatureWorking Temperature: 0 ~ 55℃ / Storage Temperature: -20 ~ 70℃
Humidity5~ 85%RH (Without condensation)
Shock ResistanceJIS C 0040 Standard
Power SupplyAC 85~265V 50 ~ 60Hz / DC 24V±10%
Power Outage Time10ms
Power Fuse250V 3.15A
Rush Current<15A 5ms / AC 100V; <30A 5ms / AC 200V / <15A 1ms / DC 24V
Power Consumption<35W
Power OutputDC 24V 850mA
Output TypeRelay
Output Circuit
InsulationMechanistic
Response Time<10ms

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Wecon LX3V-0806MR PLC”